We appreciate your interest in Spd Electrical Systems Inc part number ET5624, which is currently ready for procurement here on Prompt Aerospace. For your reference, part number ET5624 is listed with the NSN 5925-00-058-7941 and description “Circuitbreaker.” If this is the item you are seeking and you would like to request a quote for your comparisons, simply complete the form below with information like your desired quantity, budget, and anticipated fulfillment timeframe. We regularly respond to requests within 15 minutes of receiving them, using the details we are offered to curate the most ideal purchasing options.
Note : We Will Not Share Your Information To Any Third Parties.
If you want to explore other items produced by Spd Electrical Systems Inc under the CAGE Code 30086 or that similarly fall under the FSC 5925 Circuit Breakers, keep in mind that since we list everything with relevant information, you can easily locate related part numbers using our search engine or catalogs. We also excel at tracking down parts with long lead times or that are generally hard to find, meaning that we can serve you even if you do not see exactly what you need on our website. With all of this being said, we are ready to help you source any of the NSN 5925-00-058-7941 parts and Circuitbreaker items your operations require, so request a quote today.
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
ABHP | OVERALL LENGTH | 26.906 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 6.875 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 9.000 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.250 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 UNTHREADED HOLE |
BBRG | III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | III SPECIAL HANDLING FEATURE | MAGNETIC |
CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +750.0 TO 1600.0 AC ALL LOCATIONS |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 105.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 40.000 NOMINAL AT 300 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |